The main advantage of BOYARD Units is their size, which makes them the most compact in the world and their height reaches no more than 20 cm, which makes it possible to install them in places with limited space.
INVERTER Condensing Units – Smooth adjustment of compressor power, which guarantees durability, energy efficiency by more than 25%, low noise level, fast and accurate temperature control ±0.5°C. And there is also the possibility of connecting several units of equipment and equipment to it;
Cooling temperature from -30°C to +15°C will be provided by the exceptional versatility of the Units, which is absent in other similar cooling systems due to technical features.
BOYARD rotary refrigeration compressors are installed in all models of Units, which have significant technical and economic advantages over more traditional piston compressors.
Cooling capacity: 0.75 – 3 hp
Refrigerant: R404A/R448A/R449A/R454C, etc. as per your request
Voltage: 1 phase / 220V / 50~60Hz;
| Horizontal Frequency Conversion Unit Technical Data | ||||||||
| Model | HQSD-150KBI40(a) | HQSD-210KBI41(a) | HQSD-285KBI40(a) | HQSD-360KBI40(a) | HQSD-460KBI40(a) | HQSD-540KBI40(a) | ||
| ① Nominal Input (W) | 1200 | 1200 | 1550 | 1950 | 2550 | 2890 | ||
| Power Supply | 220V 50/60 Hz | |||||||
| Refrigerant | R404A or Equivalent | |||||||
| Refrigerant Max. (Kg) | 1,5 | 1,8 | 2,5 | 3,5 | 3,5 | 4,5 | ||
| ② Max Running Current (A) | 6 | 6 | 10,5 | 13,5 | 16,5 | 20 | ||
| Evap. Temp (°C) | -40 ~ -5°C | |||||||
| Ambient Temp (°C) | 10 ~ 43°C | |||||||
| Compressor (Model) | JHSD150Z312 | JHSD150Z312 | KHSD203Z312 | KHSD300Z312 | KHSD300Z312 | THSD456Z312 | ||
| Condenser | Style | Copper tube fin condenser or microchannel condenser | ||||||
| Fam Motor | Diameter (mm) | φ230*2 (EC) | φ230*2 (EC) | φ230*3 (EC) | φ230*3 (EC) | φ230*4 (EC) | φ254*4 (EC) | |
| Air Flow (m3/hr) | 730*2 | 730*2 | 730*3 | 730*3 | 730*4 | 840*4 | ||
| Basic configuration | Pressure Controller (Mpa) | Diaphragm type: high pressure switch, Low Pressure Sensor | ||||||
| Reservoir | 0,6L | 0,8L | 1,1L | |||||
| Oil separator | BLR/A-W 55833 | |||||||
| Accumulator | 650CC | 1200CC | 1L | |||||
| Dryer filter | 083S | |||||||
| Liquid Valve | 1/4 | |||||||
| Variable frequency control function | Compressor frequency control, electronic expansion valve control, condensing fan control, defrosting control, high and low pressure protection, spray control, exhaust temperature protection, current protection and fault code output. | |||||||
| Pipe (mm) | Gas Inlet Diam OD | φ12.7(1/2″) | φ15.88(5/8″) | |||||
| Liquid Outlet OD | φ9. 53(3/8” ) | |||||||
| Out Dimension (mm) | Length (mm) | 680 | 790 | 940 | 1145 | 1350 | 1350 | |
| Width (mm) | 600 | 600 | 600 | 600 | 600 | 600 | ||
| Height (mm) | 251 | 285 | ||||||
| Weight (Kg) | 29,5 | 33,5 | 47 | 53 | 62 | 66 | ||
| Noise value (dB) | 58 | 60 | 61 | 59 | 63 | 64 | ||
| Capacity (W) | Evap Temp (°C) | Ambient Temp:32°C Sub-cooling 0°C | ||||||
| -40 | 460 | 590 | 840 | 990 | 1320 | 1420 | ||
| -35 | 570 | 720 | 1040 | 1260 | 1570 | 1700 | ||
| -30 | 720 | 910 | 1250 | 1600 | 2000 | 2150 | ||
| -25 | 900 | 1150 | 1500 | 1950 | 2400 | 2600 | ||
| -20 | 1110 | 1410 | 1890 | 2450 | 2960 | 3240 | ||
| -15 | 1340 | 1700 | 2240 | 3050 | 3200 | 3700 | ||
| -10 | 1580 | 2000 | 2650 | 3650 | 4300 | 4720 | ||
| -5 | 1820 | 2320 | 2950 | 4230 | 5150 | 5600 | ||
| Wiring Capacity | Leak Protector | Rated Current (A) | 15 | 15 | 20 | 20 | 20 | 20 |
| Leak Current (mA) | 30 | 30 | 30 | 30 | 30 | 30 | ||
| Diameter (mm2) | L≤10m | 2,0 | 2,0 | 4,0 | 4,0 | 4,0 | 4,0 | |
| 10<L≤20m | 2,5 | 2,5 | 6,0 | 6,0 | 6,0 | 6,0 | ||
| 20<L≤30m | 2,5 | 2,5 | 6,0 | 6,0 | 6,0 | 6,0 | ||
| ①Refrigerating capacity test condition; ②The biggest running current test condition | ||||||||
| TEST CONDITION (GB/T 21363-2008) : | ||||||||
| TEST CATION | AMBIENT TEMP. | Sub-cooling | RETURN GAS TEMP. | EVAP. TEMP. | TESTING POWER SUPPLY | |||
| ① | STANDARD TEST CONDITIONS | 32°C | 0°C | 18°C | `-7°C | 220V—50HZ | ||
| ② | OVERLOAD RUNNING | 43°C | 0°C | 18°C | 0°C | 198V—50HZ | ||
①When the unit is used in freezing condition, it is recommended to add refrigeration solenoid valve
and use negative pressure shutdown scheme;When used in refrigeration conditions, it is recommended
to add refrigeration solenoid valve;
②Refrigerating capacity test condition;
③When the unit filling refrigerant exceeds the maximum filling amount, the quality of filling chilled oil
should be confirmed with our company.
④The biggest running current test condition;
⑤When the ambient temperature is lower than 10℃, the condensation temperature control needs to be
added;